TEMPERATURE CONTROLLER/MONITOR
Model : PTM-9957
FEATURES
* Thermocouple Temp. sensor : type K/J/T/E/R/S. Operating g 0 to 50 ℃.
* Pt Temp. sensor : Pt 100 ohm. Temperature
* Type K range : -100 to 1300 ℃, ℃/℉. Operating Less than 80% R.H.
Type J range : -100 to 1150 ℃, ℃/℉. Humidity
Type T range : -100 to 400 ℃, ℃/℉. Power Supply 90 to 260 ACV, 50/60 Hz.
Type E range : -100 to 900 ℃, ℃/℉. Power Approx. 3.3 VA/AC 110V.
Type R range : 0 to 1700 ℃, ℃/℉. Consumption Approx. 5.5 VA/AC 220V.
Type S range : 0 to 1500 ℃, ℃/℉. Weight 384 g/ 0.84 LB.
* Pt 100 ohm range : -199 to 850 ℃, ℃/℉. Dimension DIN size : 96 x 48 mm, Depth : 110 mm.
* Resolution : 0.1 degree ( < 1000 degree ) Accessories Instruction manual.............................. 1 PC
1 degree ( ≧1000 degree ) Included Case holder with screw............................2 PCs
* Control setting, Hi/Lo alarm setting. Optional Type K Temp. probe :
* Control relay output, alarm relay output. Accessories TP-01, TP-02A, TP-03, TP-04, TP-05
* Control Relay will make action when the reading value Pt 100 ohm Temp. probe : TP-100B.
reach to control value. * Data Acquisition software,
* Alarm Relay will make action when the reading value SW-U801-WIN.
reach to high/low alarm value. * RS232 cable, UPCB-02.
* Hysteresis value setting for control and alarm function. * USB cable, USB-01.
* PoMicroprocessor circuit ensures high accuracy and * Real time SD card datalogger
provides special functions and features. DL-9602SD
* Power : 90 ACV to 264 ACV, 50/60 Hz. * GSM controller, GSM-889.
* RS-232/USB computer interface. * Interface cable ( cable between meter
* DIN size : 96 x 48 mm. Depth : 107 mm. to GSM-889 ), GMCB-89.
* Optional type K probe : TP-01, TP-02A, TP-03, TP-04,
TP-05. ELECTRICAL SPECIFICATIONS
* Optional Pt 100 ohm probe : TP-100B.
* Optional USB cable, USB-01. PT 100 ohm
* Optional date acquisition software,SW-U801-WIN. Resolution Range Accuracy
0.1 ℃ -199.9 to 850.0 ℃ ± ( 0.4 % + 1 ℃ )
GENERAL SPECIFICATIONS 0.1 ℉ -327.0 to 999.9 ℉ ± ( 0.4 % + 1.8 ℉ )
Display 4 digits red LED, digit size : 14 mm. 1 ℉ 1000 to 1562 ℉ ± ( 0.4 % + 2 ℉ )
Circuit Custom chip of microprocessor LSI Type K/J/T/E/R/S
circuit. Sensor Resolu- Range Accuracy
Temp. Thermocouple Temp. sensor : Type tion
Sensor type Type K/J/T/E/R/S. Type K 0.1 ℃ -50.1 to -100.0 ℃ ± ( 0.4 % + 1 ℃ )
Pt Temp. sensor : Pt 100 ohm. -50.0 to 999.9 ℃ ± ( 0.4 % + 0.5 ℃ )
* Sensor type can make the internal 1 ℃ 1000 to 1300 ℃ ± ( 0.4 % + 1 ℃ )
setting with default 0.1 ℉ -58.1 to -148.0 ℉ ± ( 0.4 % + 1.8 ℉ )
Display units ℃,℉. -58.0 to 999.9 ℉ ± ( 0.4 % + 1 ℉ )
Offset adjust It can make the internal Offset setting 1 ℉ 1000 to 2372 ℉ ± ( 0.4 % + 2 ℉ )
with default. Type J 0.1 ℃ -50.1 to -100.0 ℃ ± ( 0.4 % + 1 ℃ )
Gain adjust It can make the internal Gain setting -50.0 to 999.9 ℃ ± ( 0.4 % + 0.5 ℃ )
with default 1 ℃ 1000 to 1150 ℃ ± ( 0.4 % + 1 ℃ )
Sampling Time Approx. 1 second. 0.1 ℉ -58.1 to -148.0 ℉ ± ( 0.4 % + 1.8 ℉ )
Relay Output Number 2 relays -58.0 to 999.9 ℉ ± ( 0.4 % + 1 ℉ )
Function Relay 1 : 1 ℉ 1000 to 2102 ℉ ± ( 0.4 % + 2 ℉ )
Control relay. Type T 0.1 ℃ -50.1 to -100.0 ℃ ± ( 0.4 % + 1 ℃ )
Relay 2 : -50.0 to 400.0 ℃ ± ( 0.4 % + 0.5 ℃ )
High/Low alarm relay. 0.1 ℉ -58.1 to -148.0 ℉ ± ( 0.4 % + 1.8 ℉ )
Max load 0.5 ACA/250 ACV -58.0 to 752.0 ℉ ± ( 0.4 % + 1 ℉ )
0.5 DCA/24 DCV Type E 0.1 ℃ -50.1 to -100.0 ℃ ± ( 0.4 % + 1 ℃ )
*Do not apply the relay -50.0 to 900.0 ℃ ± ( 0.4 % + 0.5 ℃ )
contact load current 0.1 ℉ -58.1 to -148.0 ℉ ± ( 0.4 % + 1.8 ℉ )
> 0.5 A, other wise the -58.0 to 999.9 ℉ ± ( 0.4 % + 1 ℉ )
relay may be damaged 1 ℉ 1000 to 1652 ℉ ± ( 0.4 % + 2 ℉ )
permanently without Type R 1 ℃ 0 to 1700 ℃ ± ( 0.5 % + 3 ℃ )
warranty.
Setting 1st layer CtLo ( Control low limit ) 1 ℉ 32 to 3092 ℉ ± ( 0.5 % + 5 ℉ )
Function setting CtHi ( Control high limit )
procedures ALLo ( Alarm low limit ) Type S 1 ℃ 0 to 1500 ℃ ± ( 0.5 % + 3 ℃ )
ALHi ( Alarm high limit )
Second layer tyPE ( Sensor type ) 1 ℉ 32 to 2732 ℉ ± ( 0.5 % + 5 ℉ )
dEG ( ℃, ℉ )
setting FiLt ( Digital filter ) Remark :
procedures CtHy ( Control hysteresis set ) a. Accuracy value is specified for the meter only.
ALHy ( Alarm hysteresis set ) b. Accuracy is tested under the meter's environment temperature
oFSt ( Offset adjustment ) within 23 ± 5℃.
GAin ( Gain adjustment ) c. Linearity Correction :
Data Output RS 232 PC serial interface. Memorize the thermocouple's curve into the intelligent CPU
circuit,